17. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER, A185. ALL SPUCES SHALL BE CLASS B TENSION SPU
<br />EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT STANDARD 90 DEGREE HOOKS, UNLESS NOTED OTHERWISE. YIELD STRENGTH (Fy) OF STANDARD DEFORMED BARS ARE
<br />EROSION AS SPECIFIED ON THE CONSTRUCTION DRAWINGS AND/OR PROJECT SPECIFICATIONS. AS FOLLOWS:
<br />18. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION CONTROL #4 BARS AND SMALLER....................................................................................40 ksi
<br />MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES #5 BARS AND LARGER ..................... ........... ..... .60 ksi
<br />6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE
<br />FOR EROSION AND SEDIMENT CONTROL ON DRAWINGS:
<br />19. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH.......................3"
<br />STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION CONCRETE EXPOSED TO EARTH OR WEATHER-
<br />OF OWNER.
<br />20. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL #5 BARS AND LARGER...................................................................................2"
<br />BARSAND SMALLER..........................................................................1-1/2"
<br />CABLES AND OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE #5
<br />CONCRETE NOT EXPOSED T.. EARTH OR WEATHER:
<br />RETURNED TO THE OWNER'S DESIGNATED LOCATION.
<br />21. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED SLAB AND WALLS.....................................................................................3/4'
<br />OM SITE ON A DAILY BASIS. BEAMS AND COLUMNS.............................................................................1-1/2"
<br />FR
<br />22. FR FILL E EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS, SNOW 7• A TOOLED EDGE OR A 3/4' CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED
<br />OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT. OTHERWISE, IN ACCORDANCE WITH ACI 301 SECTION 4.2.4.
<br />GREENFIELD GROUNDING NOTES:
<br />1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION AND AC POWER GESS) SHALL BE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER BONDING CONDUCTORS IN
<br />ACCORDANCE WITH THE NEC.
<br />2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR GROUND ELECTRODE SYSTEMS, THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND
<br />1 OG/16/.� � D?\[lG REVISED
<br />IC/07/24 DNRV REVISED PER CLIENT \LCK
<br />3 03/19/24 D',IR' REVISED PER CLIENT I.ICK
<br />'120/24OV,
<br />CROWN CASTLE USA INC SITE ACTIVITY REQUIREMENTS'
<br />GENERAL NOTES:
<br />ELECTRICAL INSTALLATION NOTES:
<br />�pFESS10Nq
<br />Q
<br />Q >�Me/
<br />1. NOTICE TO PROCEED- NO WORK SHALL COMMENCE PRIOR TO CROWN CASTLE USA INC. WRITTEN NOTICE
<br />1. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:
<br />CONTRACTOR: GENERAL CONTRACTOR RESPONSIBLE FOR CONSTRUCTION
<br />1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS , NEC AND ALL APPLICABLE
<br />FEDERAL, STATE, AND LOCAL CODES/ORDINANCES.
<br />! ! Mobile! ! !
<br />�NT
<br />TO PROCEED (NTP) AND THE ISSUANCE OF A PURCHASE ORDER. PRIOR TO ACCESSING/ENTERING THE
<br />SITE YOU MUST CONTACT THE CROWN CASTLE USA INC. NOC AT 800-788-7011 k THE CROWN CASTLE
<br />CARRIER: T -MOBILE
<br />TOWER OWNER: CROWN CASTLE USA INC.
<br />USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY
<br />2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED
<br />AND TRIP HAZARDS ARE ELIMINATED.
<br />USA INC. CONSTRUCTION MANAGER.
<br />2. "LOOK UP' - CROWN CASTLE USA INC. SAFETY CLIMB REQUIREMENT:
<br />THE INTEGRITY OF THE SAFETY CUMB AND ALL COMPONENTS OF THE CLIMBING FACILITY SHALL BE
<br />2. THESE DRAWINGS HAVE BEEN PREPARED
<br />EXERCISED UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE ENGINEERS IN THIS OR SIMILAR LOCALITIES. IT IS
<br />ASSUMED THAT THE WORK DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKPEOPLE
<br />OF THE APPLICABLE CODE STANDARDS AND REQUIREMENTS AND OF INDUSTRY
<br />3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC.
<br />4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC.
<br />4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL, AND SHALL CONFORM TO
<br />3257 EAST GUASTI ROAD, SLTITE 200
<br />ONTARIO, CA 91764
<br />CONSIDERED DURING ALL STAGES OF DESIGN, INSTALLATION, AND INSPECTION. TOWER MODIFICATION, MOUNT
<br />REINFORCEMENTS, AND/OR EQUIPMENT INSTALLATIONS SHALL NOT COMPROMISE THE INTEGRITY OR
<br />FUNCTIONAL USE OF THE SAFETY CUMB OR ANY COMPONENTS OF THE CLIMBING FACILITY ON THE
<br />WHO HAVE A WORKING KNOWLEDGE
<br />ACCEPTED STANDARD GOOD PRACTICE. AS NOT EVERY CONDITION OR ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN
<br />ON THESE DRAWINGS, THE CONTRACTOR SHALL USE INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR
<br />MISCELLANEOUS WORK NOT EXPLICITLY SHOWN.
<br />REQUIREMENT OF THE NATIONAL ELECTRICAL CODE.
<br />4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT
<br />CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, 22,000 AIC MINIMUM. VERYIFY AVAILABLE SHORT CIRCUIT CURRENT DOES
<br />TI IS A VIOLATION OF LAW FOR ANY PERSON,
<br />UNLESS THEY ARE AC IrLNG UNDER THE DIRECTION
<br />OF A LICENSED PROFESSIONAL ENGINEER,
<br />STRUCTURE. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO: PINCHING OF THE WIRE ROPE, BENDING OF
<br />THE WIRE ROPE FROM ITS SUPPORTS, DIRECT CONTACT OR CLOSE PROXIMITY TO THE WIRE ROPE WHICH
<br />MAY CAUSE FRICTIONAL WEAR, IMPACT TO THE ANCHORAGE POINTS IN ANY WAY, OR TO IMPEDE/BLOCK ITS
<br />3. THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHODS OF
<br />CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS,
<br />FOR
<br />NOT EXCEED THE RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT
<br />ADOPTED CODE PRE THE GOVERNING JURISDICTION.
<br />5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE
<br />_�y. CROWN
<br />INTENDED USE ANY COMPROMISED SAFETY CLIMB, INCLUDING EXISTING CONDITIONS MUST BE TAGGED OUT
<br />TECHNIQUES, SEQUENCES, AND PROCEDURES. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY
<br />PROTECTION OF LIFE AND PROPERTY DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED
<br />LABELED WITH COLOR -CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2' PLASTIC ELECTRICAL TAPE WITH UV
<br />;+t'
<br />AND REPORTED TO YOUR CROWN CASTLE USA INC. POC OR CALL THE NOC TO GENERATE A SAFETY CUMB
<br />T
<br />MAINTENANCE AND CONTRACTOR NOTICE TICKET.
<br />TO, BRACING, FORMWORK, SHORING, ETC. SITE VISITS BY THE ENGINEER OR HIS REPRESENTATIVE WILL NOT INCLUDE
<br />INSPECTION OF THESE ITEMS AND IS FOR STRUCTURAL OBSERVATION OF THE FINISHED STRUCTURE ONLY.
<br />PROTECTION, OR EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA.
<br />6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE
<br />l CASTLE
<br />3. PRIOR TO THE START CONSTRUCTION, ALL REQUIRED JURISDICTIONAL PERMITS SHALL BE OBTAINED.
<br />IS NOT UNITED TO, BUILDING, ELECTRICAL, MECHANICAL FIRE, FLOOD ZONE,
<br />4. NOTES AND DETAILS IN THE CONSTRUCTION DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL
<br />NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT,
<br />CONFIGURATION, WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD AND'>
<br />ID'S).
<br />200 SPEaUJI CENTER DRIA'E,
<br />THIS INCLUDES, BUT
<br />ENVIRONMENTAL, AND ZONING. AFTER ONSITE ACTIVITIES AND CONSTRUCTION ARE COMPLETED, ALL
<br />AND CLOSED OUT ACCORDING TO LOCAL JURISDICTIONAL
<br />DETAILS. WHERE
<br />AND/OR AS PROVIDED FOR IN THE CONTRACT DOCUMENTS. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS,
<br />SHALL GOVERN. IF FURTHER
<br />CIRCUIT
<br />7• PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS.
<br />TOOL TO REMOVE SHARP EDGES.
<br />SL=, 1-00 & 1800
<br />REQUIRED PERMITS SHALL BE SATISFIED
<br />REQUIREMENTS.
<br />GENERAL NOTES, AND SPECIFICATIONS, THE GREATER, MORE STRICT REQUIREMENTS,
<br />CLARIFICATION IS REQUIRED CONTACT THE ENGINEER OF RECORD.
<br />S. ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING
<br />9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER)
<br />IRVINE, CA 92618
<br />4. ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITED TO, ERECTION PLANS, RIGGING
<br />PLANS, CLIMBING PLANS, AND RESCUE PLANS SHALL BE THE RESPONSIBILITY OF THE GENERAL
<br />5. SUBSTANTIAL EFFORT HAS BEEN MADE TO PROVIDE ACCURATE DIMENSIONS AND MEASUREMENTS ON THE DRAWINGS TO
<br />ASSIST IN THE FABRICATION AND/OR PLACEMENT OF CONSTRUCTION ELEMENTS BUT IT IS THE SOLE RESPONSIBILITY
<br />WITH TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
<br />10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR LARGER) WITH
<br />CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THE WORK CONTAINED HEREIN, AND SHALL MEET
<br />ANSI/ASSE A10.48 (LATEST EDITION); FEDERAL, STATE, AND LOCAL REGULATIONS; AND ANY APPLICABLE
<br />INDUSTRY CONSENSUS STANDARDS RELATED TO THE CONSTRUCTION ACTIVITIES BEING PERFORMED. ALL
<br />OF THE CONTRACTOR TO FIELD VERIFY THE DIMENSIONS, MEASUREMENTS, AND/OR CLEARANCES SHOWN IN THE
<br />CONSTRUCTION DRAWINGS PRIOR TO FABRICATION OR CUTTING OF ANY NEW OR EXISTING CONSTRUCTION ELEMENTS.
<br />IF IT IS DETERMINED THAT THERE ARE DISCREPANCIES AND/OR CONFLICTS WITH THE CONSTRUCTION DRAWINGS THE
<br />TYPE THHW, TOWN, L WIRIN XHHW, XHHW-2, THA, LL BE RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
<br />11• POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI -CONDUCTOR, TYPE SOOW CORD (//14 OR LARGER) UNLESS
<br />OTHERWISE SPECIFIED.
<br />Ki m 1 e>> Horn
<br />RIGGING PLANS SHALL ADHERE TO ANSI/ASSE A10.48 (LATEST EDITION) AND CROWN CASTLE USA INC.
<br />THE REQUIRED INVOLVEMENT OF A QUALIFIED ENGINEER FOR
<br />ENGINEER OF RECORD IS TO BE NOTIFIED AS SOON AS POSSIBLE.
<br />SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH THE
<br />12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL MULTI -CONDUCTOR, TYPE NL CABLE (RWI OR LARGER. WITH
<br />UNLESS OTHERWISE SPECIFIED.
<br />STANDARD CED -STD -10253, INCLUDING
<br />CLASS IV CONSTRUCTION, TO CERTIFY THE SUPPORTING STRUCTURE(S) IN ACCORDANCE WITH ANSI/TIA-322
<br />(LATEST EDITION).
<br />'INSTALLATION FOR CONSTRUCTION
<br />6. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING CONTRACTOR
<br />EXISTING CONDITIONS AND TO CONFIRM THAT THE WORK CAN BE ACCOMPLISHED AS SHOWN ON THE CONSTRUCTION
<br />DRAWINGS. ANY DISCREPANCY FOUND SHALL BE BROUGHT TO THE ATTENTION OF CROWN CASTLE.
<br />7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES,
<br />RHW, , RHW E INSULATION
<br />W,
<br />TYPE THHW, THAN, THAN -2, XHHW, XHHW-2, THA, E CRIMP -STYLE,
<br />13. ALL POWER AND GROUNDING CONNECTIONS SHALL E CRIMP -STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND
<br />BETTS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75' C (90' C IF AVAILABLE).
<br />BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE
<br />421 FA'iETTE-k,=E ST, SUITE 600
<br />5. ALL SITE WORK TO COMPLY WITH OAS -STD -10068 STANDARDS
<br />ACTIVITIES ON CROWN CASTLE USA INC. TOWER SITE,' CED -STD -10294 "STANDARD FOR INSTALLATION OF
<br />MOUNTS AND APPURTENANCES,- AND LATEST VERSION OF ANSI/TIA-1019-A-2012 -STANDARD FOR
<br />REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS,
<br />ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE
<br />OF THE WORK. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY
<br />14. RACEWAY AND CABLE TRAY SHALL
<br />AND NEC.
<br />15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT (IMC), OR RIGID METAL CONDUIT (RMC) SHALL BE USED FOR
<br />RALEIGH, NC 27GO1
<br />INSTALLATION, ALTERATION, AND MAINTENANCE OF ANTENNA SUPPORTING STRUCTURES AND ANTENNAS."
<br />6. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR
<br />SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND APPLICABLE REGULATIONS.
<br />8. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES AND
<br />EXPOSED INDOOR LOCATIONS.
<br />16. ELECTRICAL METALLIC TUBING (EMT) METAL -CLAD CABLE RAI SHALL BE USED FOR CONCEALED INDOOR LOCATIONS.
<br />PVC ON STRAIGHTS AND SCHEDULE 80 PVC UNDER ALL TRAFFIC EASEMENTS
<br />SHALL PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY CROWN CASTLE USA INC. PRIOR TO
<br />PROCEEDING WITH ANY SUCH CHANGE OF INSTALLATION.
<br />LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.
<br />9. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S
<br />17. UNDERGROUND CONDUIT SHALL BE SCHEDULE 40
<br />AND ALL ELBOWS/90s. ABOVE GRADE CONDUIT TO BE SCH 80 PVC OR IMC/RMC CONDUIT. EMT IS ALLOWED AT STUB UP
<br />7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE
<br />CODES, REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND
<br />RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.
<br />10. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL
<br />LOCATIONS AND INDOORS ONLY.
<br />18. LIQUID -TIGHT FLEXIBLE METALLIC CONDUIT (UOUID-TITE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION
<br />T -MOBILE SITE NU_i\.Q3ER:
<br />COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC
<br />AUTHORITY REGARDING THE PERFORMANCE OF THE WORK. ALL WORK CARRIED OUT SHALL COMPLY WITH
<br />PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY THE CARRIER AND CROWN CASTLE PRIOR TO PROCEEDING
<br />WITH ANY SUCH CHANGE OF INSTALLATION.
<br />OCCURS OR FLEXIBILITY IS NEEDED.
<br />19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION -TYPE AND APPROVED FOR THE LOCATION USED. SET
<br />SVO0595A
<br />ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES,
<br />ORDINANCES AND APPLICABLE REGULATIONS.
<br />11• CONTRACTOR IS TO PERFORM A SITE INVESTIGATION AND IS TO DETERMINE THE BEST ROUTING OF ALL CONDUITS FOR
<br />POWER, AND TELCO AND FOR GROUNDING CABLES AS SHOWN IN THE POWER, TELCO, AND GROUNDING PLAN
<br />SCREW FITTINGS ARE NOT ACCEPTABLE.
<br />20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND
<br />8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S
<br />RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE
<br />DRAWINGS.
<br />12. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND STRUCTURES. ANY
<br />THE NEC.
<br />21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS
<br />BL' #: 845308
<br />9. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION.
<br />DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF CROWN CASTLE USA INC.
<br />DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND
<br />(WIREMOLD SPECMATE WIREWAY).
<br />WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL).
<br />T.O. SOCCER FIELD
<br />10. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES WHERE ENCOUNTERED IN THE
<br />WORK, SHALL BE PROTECTED AT ALL TIMES AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE
<br />WORK, SHALL BE RELOCATED AS DIRECTED BY CONTRACTOR. EXTREME CAUTION SHOULD BE USED BY THE
<br />13. CONTRACTOR SHALL LEGALLY AND PROPERLY
<br />OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S
<br />DESIGNATED LOCATION.
<br />22. SLOTTED
<br />23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON -PERFORATED STRAPS AND HANGERS. EXPLOSIVE
<br />DEVICES (i.e. POWDER -ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE
<br />CONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES. CONTRACTOR SHALL
<br />14. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON
<br />A DAILY BASIS.
<br />LINES OF THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. CHANGES
<br />IN DIRECTION TO ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN
<br />2525 NORTH MOORP ARU
<br />PROVIDE SAFETY TRAINING FOR THE WORKING CREW. THIS WILL INCLUDE BUT NOT BE LIMITED TO A) FALL
<br />PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING AND EXCAVATION E)
<br />A NEAT AND WORKMANLIKE MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT
<br />SHALL BE FISHED TO CLEAR OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO
<br />ROAD
<br />CONSTRUCTION SAFETY PROCEDURES.
<br />11. ALL SITE WORK SHALL BEC INDICATED ON THE STAMPED CONSTRUCTION DRAWINGS AND PROJECT
<br />CONCRETE FOUNDATIONS, AND REINFORCING STEEL:
<br />PREVENT CONCRETE, PLASTER OR DIRT FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED
<br />MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE.
<br />TI'IOUStLND OAKS, C.1 91360
<br />SPECIFICATIONS, LATEST APPROVED REVISION.
<br />12. CONTRACTOR SHALL KEEP THE SITE FREE FROM ACCUMULATING WASTE MATERIAL DEBRIS, AND TRASH AT
<br />24. EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY-COATED SHEET
<br />STEEL SHALL MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3R (OR
<br />THE COMPLETION OF THE WORK. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER
<br />REFUSE SHALL BE REMOVED FROM RHEGASSITE
<br />1 WORK ACI 336, ASTM A184, ASTM A185 AND
<br />WITH EINCIPLACE
<br />BE ISPECIFlCATAON
<br />BETTER25. METAL RECEPTAFOR �RI�OHA�OD DEVICE BOXES SHALL BE GALVANIZED, EPDXY-COATED OR NON -CORRODING; SHALL MEET OR
<br />EZISTING 110'-0" MONOPOLE
<br />13. ALL EXISTING INACTIVE SEWER, WATER, ELECTRIC AND OTHER UTILITIES WHICH INTERFERE WITH THE
<br />EXECUTION OF THE WORK, SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUED
<br />AT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL
<br />OWNER, CROWN CASTLE USA INC., AND/OR LOCAL UTILITIES.
<br />NCRETE.ACI
<br />FOR CASTNCE
<br />THE DESIGN ANDCONsucnlON CO
<br />2. UNLESS NOTED OTHERWISE, SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED
<br />TO BE 1000 psf.
<br />3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (f'c) OF 3000 psi AT 28 DAYS, UNLESS NOTED
<br />EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED
<br />(WP OR BETTER) FOR EXTERIOR LOCATIONS.
<br />26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) AND BE RATED
<br />OF CONTRACTOR, TOWER
<br />14. THE CONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATION FOR
<br />SITE SIGNAGE REQUIRED BY LOCAL JURISDICTION AND SIGNAGE REQUIRED ON INDIVIDUAL PIECES OF
<br />EQUIPMENT, ROOM S, AND SHELTERS.
<br />S, LT CAUSE SURFACE WATER TO FLOW AWAY FROM THE CARRIER'S EQUIPMENT
<br />OTHERWISE. NO MORE THAN 90 MINUTES SHALL ELAPSE FROM BATCH TIME TO TIME OF PLACEMENT UNLESS
<br />APPROVED BY THE ENGINEER OF RECORD. TEMPERATURE OF CONCRETE SHAD_ NOT EXCEED 90Y AT TIME OF
<br />PLACEMENT.
<br />4. CONCRETE EXPOSED TO FREEZE -THAW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXTURES. AMOUNT OF AIR
<br />NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS.
<br />27• THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR CROWN CASTLE USA INC.
<br />BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS.
<br />28, THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN ACCORDANCE
<br />ISSUED FOR:
<br />I
<br />15. THE SITE SHALL GRADED
<br />AND TOWER AREAS.
<br />ENTRAINMENT TO BE BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE). CEMENT USED TO BE
<br />TYPE II PORTLAND CEMENT WITH A MAXIMUM WATER -TO -CEMENT RATIO (W/C) OF 0.45.
<br />WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY.
<br />29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW 'T -MOBILE".
<br />REV DATE DR\\N DESCF=ION IDES/Q
<br />IPER
<br />16. THE SUB GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO FINISHED
<br />SURFACE APPLICATION.
<br />5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615. ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM
<br />CES UNLESS NED OTOTHERWISE ALL HOOKS SHALL BE
<br />30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED.
<br />0 11/28/_ DRD ISSUED FOR CONSTR 1Ir_K
<br />CLIENT I \ICK
<br />17. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER, A185. ALL SPUCES SHALL BE CLASS B TENSION SPU
<br />EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT STANDARD 90 DEGREE HOOKS, UNLESS NOTED OTHERWISE. YIELD STRENGTH (Fy) OF STANDARD DEFORMED BARS ARE
<br />EROSION AS SPECIFIED ON THE CONSTRUCTION DRAWINGS AND/OR PROJECT SPECIFICATIONS. AS FOLLOWS:
<br />18. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION CONTROL #4 BARS AND SMALLER....................................................................................40 ksi
<br />MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES #5 BARS AND LARGER ..................... ........... ..... .60 ksi
<br />6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE
<br />FOR EROSION AND SEDIMENT CONTROL ON DRAWINGS:
<br />19. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH.......................3"
<br />STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION CONCRETE EXPOSED TO EARTH OR WEATHER-
<br />OF OWNER.
<br />20. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL #5 BARS AND LARGER...................................................................................2"
<br />BARSAND SMALLER..........................................................................1-1/2"
<br />CABLES AND OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE #5
<br />CONCRETE NOT EXPOSED T.. EARTH OR WEATHER:
<br />RETURNED TO THE OWNER'S DESIGNATED LOCATION.
<br />21. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED SLAB AND WALLS.....................................................................................3/4'
<br />OM SITE ON A DAILY BASIS. BEAMS AND COLUMNS.............................................................................1-1/2"
<br />FR
<br />22. FR FILL E EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS, SNOW 7• A TOOLED EDGE OR A 3/4' CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED
<br />OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT. OTHERWISE, IN ACCORDANCE WITH ACI 301 SECTION 4.2.4.
<br />GREENFIELD GROUNDING NOTES:
<br />1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION AND AC POWER GESS) SHALL BE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER BONDING CONDUCTORS IN
<br />ACCORDANCE WITH THE NEC.
<br />2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR GROUND ELECTRODE SYSTEMS, THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND
<br />ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS.
<br />3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE
<br />1 OG/16/.� � D?\[lG REVISED
<br />IC/07/24 DNRV REVISED PER CLIENT \LCK
<br />3 03/19/24 D',IR' REVISED PER CLIENT I.ICK
<br />'120/24OV,
<br />-• •
<br />X4.4 , C10- 0�
<br />•
<br />�pFESS10Nq
<br />Q
<br />Q >�Me/
<br />COMMUNICATION, ALARM OR
<br />CABLES, OR CONDUIT AND TRAFFIC LOOPS
<br />\G ,/
<br />4
<br />=C.y `-Q C� -,
<br />`I
<br />POTABLE WATER
<br />W
<br />�R, IRRIGATION, AND
<br />YINES
<br />SLURRY
<br />r,' a SEWERS AND DRAIN LINES
<br />ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS.
<br />3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE
<br />1 OG/16/.� � D?\[lG REVISED
<br />IC/07/24 DNRV REVISED PER CLIENT \LCK
<br />3 03/19/24 D',IR' REVISED PER CLIENT I.ICK
<br />APWA UNIFORM COLOR CODE:
<br />PROPOSED EXCAVATION
<br />4 w/12/24 j D%IW REVISED PERCLIsvr SICK
<br />X4.4 , C10- 0�
<br />TEMPORARY SURVEY MARKINGS
<br />ELECTRIC POWER LINES, CABLES,
<br />CONDUIT, AND LIGHTING CABLES
<br />GAS, OIL, STEAM, PETROLEUM, OR
<br />GASEOUS MATERIALS
<br />SIGNAL ONES,
<br />�pFESS10Nq
<br />Q
<br />Q >�Me/
<br />COMMUNICATION, ALARM OR
<br />CABLES, OR CONDUIT AND TRAFFIC LOOPS
<br />\G ,/
<br />4
<br />=C.y `-Q C� -,
<br />`I
<br />POTABLE WATER
<br />W
<br />�R, IRRIGATION, AND
<br />YINES
<br />SLURRY
<br />r,' a SEWERS AND DRAIN LINES
<br />C 94589
<br />ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS.
<br />3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE
<br />s SEE NEC 210.5(C)(1) AND (2)
<br />ss POLARITY MARKED AT TERMINATION
<br />�J►
<br />TESTING RESULTS.
<br />4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH #6 COPPER WIRE UL APPROVED GROUNDING TYPE CONDUIT
<br />ABBREVIATIONS:
<br />X4.4 , C10- 0�
<br />CLAMPS.
<br />5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR. STRANDED COPPER CONDUCTORS WITH GREEN INSULATION, SIZED IN ACCORDANCE WITH THE NEC, SHALL BE FURNISHED AND INSTALLED
<br />ANT ANTENNA
<br />OF CA
<br />WITH THE POWER CIRCUITS TO BTS EQUIPMENT.
<br />6. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL EQUIPMENT GROUND WIRES, #6 STRANDED COPPER OR LARGER FOR INDOOR BTS; #2 BARE SOLID TINNED
<br />(E) EXISTING
<br />COPPER FOR OUTDOOR BTS.
<br />FIF FACILITY INTERFACE FRAME
<br />GEN GENERATOR
<br />04/12/24
<br />7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE OF THE GROUND BUS ARE PERMITTED.
<br />BARS AND THE GROUND RING SHALL BE #2 SOLID TINNED COPPER UNLESS OTHERWISE INDICATED.
<br />GPS GLOBAL POSITIONING SYSTEM
<br />Exp. 03/31/25
<br />B. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND
<br />9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS.
<br />10. USE OF 90' BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45' BENDS CAN BE ADEQUATELY SUPPORTED.
<br />11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE.
<br />SHALL BE FORMED USING HIGH PRESS CRIMPS.
<br />GSM GLOBAL SYSTEM FOR MOBILE
<br />LTE LONG TERM EVOLUTION
<br />MGB MASTER GROUND BAR
<br />MW MICROWAVE
<br />12. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR)
<br />13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS.
<br />14. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE AND THE TOWER GROUND BAR.
<br />15. APPROVED ANTIOXIDANT COATINGS (i.e. CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND CONNECTIONS.
<br />16. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL.
<br />17. MISCELLANEOUS ELECTRICAL AND NON -ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN ACCORDANCE WITH THE NEC.
<br />NEW
<br />NEC NATIONAL ELECTRIC CODE
<br />(P) PROPOSED
<br />pP POWER PLANT
<br />QT, QUANTITY
<br />RECT RECTIFIER
<br />TI IS A VIOLATION OF LAW FOR ANY PERSON,
<br />UNLESS THEY ARE AC IrLNG UNDER THE DIRECTION
<br />OF A LICENSED PROFESSIONAL ENGINEER,
<br />18. BOND ALL METALLIC OBJECTS WITHIN 6 ft OF MAIN GROUND RING WITH (1) #2 BARE SOLID TINNED COPPER GROUND CONDUCTOR.TO
<br />USED FOR THE FACILITY GROUNDING AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR, SUCH AS METALLIC CONDUITS,
<br />RBS RADIO BASE STATION
<br />ALTER THIS DOCUNIENT
<br />19. GROUND CONDUCTORS
<br />METAL SUPPORT CUPS OR SLEEVES THROUGH WALLS OR FLOORS. WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS, NON-METALUC MATERIAL SUCH AS PVC CONDUIT SHALL BE
<br />E CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT.
<br />RET REMOTE ELECTRIC TILT
<br />REDS RADIO FREQUENCY DATA SHEET
<br />SHEET NUER: REVISION:
<br />b113
<br />USED. WHERE USE OF METAL CONDUIT IS UNAVOIDABLE i.e., NONMETALUC CONDUIT PROHIBITED BY LOCAL CODE GROUND
<br />( ) THE
<br />2D. ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE #2 BARE SOLID TINNED COPPER IN 3/4" NON-METALUC, FLEXIBLE CONDUIT FROM 24' BELOW GRADE TO WITHIN 3' TO 6' OF CAD -WELD TERMINATION
<br />POINT. THE EXPOSED END OF THE CONDUIT MUST BE SEALED WITH SILICONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL).
<br />21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE, THE CONTRACTOR SHALL ROUTE TWO GROUNDING CONDUCTORS FROM THE ROOFTOP, TOWERS, AND WATER TOWERS GROUNDING RING, TO
<br />RRH REMOTE RADIO HEAD
<br />RRU REMOTE RADIO UNIT
<br />SIAD SMART INTEGRATED DEVICE
<br />TMA TOWER MOUNTED AMPLIFIER
<br />T-2 4
<br />THE EXISTING GROUNDING SYSTEM, THE GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER. ROOFTOP GROUNDING RING SHALL BE BONDED TO THE EXISTING GROUNDING SYSTEM, THE BUILDING STEEL COLUMNS,
<br />TYP TYPICAL
<br />UGHTNING PROTECTION SYSTEM, AND BUILDING MAIN WATER LINE (FERROUS OR NONFERROUS METAL PIPING ONLY).
<br />UMTS UNIVERSAL MOBILE TELECOMMUNICATIONS SYSTEM
<br />W.P. WORK POINT